| Name | Value | Unit | Watch |
|---|---|---|---|
| LT Suction Pressure | 9.02 | Bar |
|
| MT Suction Pressure | 31.71 | Bar |
|
| Discharge Pressure | 79.4 | Bar |
|
| Oil Reservoir Pressure | 35.9 | Bar |
|
| Receiver Pressure | 31.1 | Bar |
|
| LT Suction Temp | -4.8 | Deg. C |
|
| LT Discharge Temp | 27.7 | Deg. C |
|
| MT Suction Temp | 18.5 | Deg. C |
|
| MT Discharge Temp | 84.4 | Deg. C |
|
| GC Leaving Temp | 25.8 | Deg. C |
|
| Ambient Temp | 23.7 | Deg. C |
|
| Temp Probe 1 | -33.6 | Deg. C |
|
| Temp Probe 2 | 28.9 | Deg. C |
|
| LT Comp1 HP Fault | On |
|
|
| LT Comp1 Oil Fault | Off |
|
|
| LT Comp1 OL Fault | Off |
|
|
| LT Comp1 INV Fault | Off |
|
|
| LT Comp2 HP Fault | On |
|
|
| LT Comp2 Oil Fault | Off |
|
|
| LT Comp2 OL Fault | Off |
|
|
| LT Comp2 INV Fault | Off |
|
|
| LT Comp3 HP Fault | On |
|
|
| LT Comp3 Oil Fault | Off |
|
|
| LT Comp3 OL Fault | Off |
|
|
| LT LP Safety SW | On |
|
|
| MT Comp1 HP Fault | On |
|
|
| MT Comp1 Oil Fault | Off |
|
|
| MT Comp1 OL Fault | Off |
|
|
| MT Comp1 INV Fault | Off |
|
|
| MT Comp2 HP Fault | On |
|
|
| MT Comp2 Oil Fault | Off |
|
|
| MT Comp2 OL Fault | Off |
|
|
| MT Comp3 HP Fault | On |
|
|
| MT Comp3 Oil Fault | Off |
|
|
| MT Comp3 OL Fault | Off |
|
|
| MT LP Safety SW | On |
|
|
| Receiver Low Level Fault | On |
|
|
| Receiver High Level Fault | Off |
|
|
| Oil Reservoir Low Level Fault | On |
|
|
| Desuperheater Fan Fault | On |
|
|
| GC Fan Fault | On |
|
|
| Remote Switch | On |
|
|
| Auto-Off Signal | On |
|
|
| Supply Voltage | 213.5 | V |
|
| Current | 73.7 | A |
|
| Power Factor | 0.79 | % |
|
| System Power | 9.2 | kW |
|
| Total Energy | 0.0 | kWhr |
|
| Frequency | 50.0 | Hz |
|
| Name | Value | Unit | Watch |
|---|---|---|---|
| LT Suction Press Setpoint | 9.0 | Bar |
|
| LT Suction Superheat | 35.3 | K |
|
| LT SH Setpoint | 18.0 | K |
|
| LT Comp1 On | On |
|
|
| LT Comp1 Start-Stop Timer | Off |
|
|
| LT Comp1 Stop-Start Timer | Off |
|
|
| LT Comp1 Min Freq Start Timer | Off |
|
|
| LT Comp1 Speed | 33.33 | % |
|
| LT Comp1 Freq | 50.0 | Hz |
|
| LT INV1 Reset | Off |
|
|
| LT Comp1 Current Displacement | 9.2 | m³/hr |
|
| LT Comp1 Starts per Day | 2 |
|
|
| LT Comp1 Starts Per Month | 25 |
|
|
| LT Comp1 Hrs | 15759.4 | Hrs |
|
| LT Comp2 On | On |
|
|
| LT Comp2 Start-Stop Timer | Off |
|
|
| LT Comp2 Stop-Start Timer | Off |
|
|
| LT Comp2 Speed | 54.33 | % |
|
| LT Comp2 Freq | 56.3 | Hz |
|
| LT INV2 Reset | Off |
|
|
| LT Comp2 Current Displacement | 10.4 | m³/hr |
|
| LT Comp2 Starts per Day | 1 |
|
|
| LT Comp2 Starts Per Month | 23 |
|
|
| LT Comp2 Hrs | 15686.8 | Hrs |
|
| LT Comp3 On | Off |
|
|
| LT Comp3 Start-Stop Timer | Off |
|
|
| LT Comp3 Stop-Start Timer | Off |
|
|
| LT Comp3 Starts per Day | 32 |
|
|
| LT Comp3 Starts Per Month | 248 |
|
|
| LT Comp3 Hrs | 8288.8 | Hrs |
|
| LT Total Used Percentage | 55.9 | % |
|
| LT Electronic LP Alarm | Off |
|
|
| LT LP Shutdown Per Day | 0 |
|
|
| LT Electronic HP Alarm | Off |
|
|
| LT HP Shutdown Per Day | 0 |
|
|
| LT Suc Reheat Valve Close | Off |
|
|
| LT Suc Reheat Valve Open | Off |
|
|
| Suction Superheat Valve Status | 0 |
|
|
| MT Suction Press Setpoint | 31.7 | Bar |
|
| MT Suction Superheat | 20.8 | K |
|
| MT SH Setpoint | 18.0 | K |
|
| MT Comp1 On | On |
|
|
| MT Comp1 Start-Stop Timer | Off |
|
|
| MT Comp1 Stop-Start Timer | Off |
|
|
| MT Comp1 Min Freq Start Timer | Off |
|
|
| MT Comp1 Min Freq Timer | Off |
|
|
| MT Comp1 Speed | 68.00 | % |
|
| MT Comp1 Freq | 55.6 | Hz |
|
| MT INV1 Reset | Off |
|
|
| MT Comp1 Hrs | 16041 | Hrs |
|
| MT Comp1 Current Displacement | 7.2 | m³/hr |
|
| MT Comp1 Starts Per Day | 1 |
|
|
| MT Comp1 Starts Per Month | 30 |
|
|
| MT Comp2 On | Off |
|
|
| MT Comp2 Start-Stop Timer | Off |
|
|
| MT Comp2 Stop-Start Timer | Off |
|
|
| MT Comp2 Starts per Day | 46 |
|
|
| MT Comp2 Starts Per Month | 449 |
|
|
| MT Comp2 Hrs | 3400 | Hrs |
|
| MT Comp3 On | Off |
|
|
| MT Comp3 Start-Stop Timer | Off |
|
|
| MT Comp3 Stop-Start Timer | Off |
|
|
| MT Comp3 Starts per Day | 39 |
|
|
| MT Comp3 Starts Per Month | 311 |
|
|
| MT Comp3 Hrs | 3312 | Hrs |
|
| MT Total Used Percentage | 32.7 | % |
|
| MT Electronic LP Alarm | Off |
|
|
| MT LP Shutdown Per Day | 0 |
|
|
| MT Electronic HP Alarm | Off |
|
|
| MT HP Shutdown Per Day | 0 |
|
|
| DSH Fan On | On |
|
|
| DSH Fans Output | 100.0 | % |
|
| Oil Reservoir Fill Valve | Off |
|
|
| Oil Reservoir Relief Valve | Off |
|
|
| Oil Res. Fill Valve Cyc Per Hr | 0 |
|
|
| Oil Res. Relief Valve Cyc Per H | 0 |
|
|
| Alarm Out | On |
|
|
| Subcritical Mode | Off |
|
|
| Transcritical Mode | On |
|
|
| SC to TC Activation Timer | Off |
|
|
| TC to SC Activation Timer | Off |
|
|
| GC Target Leaving Temp | 25.7 | Deg. C |
|
| GC Target Pressure | 78.7 | Bar |
|
| GC Fans Output | 52.6 | % |
|
| GC Fan On | On |
|
|
| HPCV | 37.1 | % |
|
| EEV Driver Control | On |
|
|
| Turn On Signal | On |
|
|
| Pump Down Signal | Off |
|
|
| Inhibit Signal | Off |
|
|
| Shut Down Signal | Off |
|
|
| Room Temp Setpoint | 30.0 | Deg. C |
|
| Room Temp High Setpoint | -28.0 | Deg. C |
|
| Temp Alarm | 0 |
|
|
| Temp Alarm Output | On |
|
|
| Adiabatic Cooling Run | Off |
|
|
| Adiabatic Cooling Fault | Off |
|
|
| Energy Per Day | 0.0 | kWhr |
|
| Energy Per Month | 0.0 | kWhr |
|
| Adiabatic Cooling Proof | Off |
|
| Name | Value | Unit | Watch |
|---|---|---|---|
| LT Suction Press Setpoint | 9.00 | Bar |
|
| LT Comp2 Stop-Start Time | 60 | secs |
|
| LT LP Shutdown Setpoint | 6.5 | Bar |
|
| LT LP deadband | 1.0 | Bar |
|
| LT HP Shutdown Setpoint | 43.0 | Bar |
|
| LT HP Deadband | 1.0 | Bar |
|
| LT Pump Down Setpoint | 7.30 | Bar |
|
| LT Inh Max Pressure | 26.0 | Bar |
|
| MT Suction Press Setpoint | 31.7 | Bar |
|
| MT LP Shutdown Setpoint | 21.8 | Bar |
|
| MT LP deadband | 2.0 | Bar |
|
| MT LP Shutdown delay | 2 | secs |
|
| MT HP Shutdown Setpoint | 100.0 | Bar |
|
| MT HP Deadband | 1.0 | Bar |
|
| MT Suc SH Setpoint | 18.0 | K |
|
| MT Inh Max Pressure | 40.0 | Bar |
|
| Room Temp SP | 30.0 | Deg. C |
|
| Room Temp High SP | -28.0 | Deg. C |
|
| Room Temp Alarm Delay | 5.0 | Min |
|
| Temp Start Delay Timer | 90.0 | Min |
|
| Adiabatic Cooling Delay Start | 20 | secs |
|
| Adiabatic fan Speed Adjust | 100.0 | % |
|
| GCLT Adiabatic Cooling Stop Tem | 30.0 | Deg. C |
|
| GCLT Adiabatic Cooling Start Te | 35.0 | Deg. C |
|
| Compressors Quantity | 3 LT + 3 MT |
|
|
| Refrigerant | R744 CO2 |
|